Stationary

UP-UPS Series

UP-UPS Series

UPS

Design life
15 years at 20°C.
Water refilling
More than 3 years at 20°C.
IIEC 896-1
1000 cycles.
Self discharge
Approx. 3% per month at 20°C.
Operating temperature range
-20°C to 55°C, recommended 10°C to 30°C.
Full conformity with
DIN 40736-3, IIEC 896-1 & VDE 0510-2.

Main uses

  • Line control centers.
  • Signaling systems.
  • Lighting systems.
  • Cold-start of diesel generators
          of electricity.
  • Emergency lighting.
  • etc ...

Specifications

Model Capacity Ah 1.80
UPC 20ºC
Length
(mm/inch)
Width
(mm/inch)
Height
(mm/inch)
Weight IR mΩ Short Circuit
Current (A)
Data Sheet
(PDF)
C10 C1 Wet
(kg)
Dry
(kg)
00012V 1 UPS 100 41 130 272 / 10.71 205 / 8.07 392 / 15.43 33 22 16,80 0,73
01012V 2 UPS 200 59 219 272 / 10.71 205 / 8.07 392 / 15.43 41 30,1 8,40 1,46
01112V 3 UPS 300 86 317 272 / 10.71 205 / 8.07 392 / 15.43 49 38,2 5,60 2,20
01212V 4 UPS 400 114 417 272 / 10.71 205 / 8.07 392 / 15.43 58 47,3 4,20 2,93
01312V 5 UPS 500 147 513 380 / 14.96 205 / 8.07 392 / 15.43 78 62,3 3,06 3,66
01412V 6 UPS 600 179 619 380 / 14.96 205 / 8.07 392 / 15.43 86 70,5 2,80 4,39
01512V 7 UPS 700 206 728 272 / 10.71 205 / 8.07 392 / 15.43 49 37,1 1,20 5,13
0166V 8 UPS 800 247 422 272 / 10.71 205 / 8.07 392 / 15.43 53 41,9 1,05 5,86
0176V 9 UPS 900 271 468 380 / 14.96 205 / 8.07 392 / 15.43 68 52 0,93 6,59
0186V 10 UPS 1000 293 518 380 / 14.96 205 / 8.07 392 / 15.43 72 57 0,84 7,32
0196V 11 UPS 1100 325 572 380 / 14.96 205 / 8.07 392 / 15.43 75 59 0,76 8,05
0206V 12 UPS 1200 347 624 380 / 14.96 205 / 8.07 392 / 15.43 86 63 0,70 8,79
0212V 24 UPS 2400 742 422 205 / 8.07 272 / 10.71 392 / 15.43 53 41,9 0,13 17,58
0222V 30 UPS 3000 829 518 205 / 8.07 380 / 14.96 392 / 15.43 72 57 0,10 21,90
0232V 36 UPS 3600 1041 624 205 / 8.07 380 / 14.96 392 / 15.43 86 63 0,08 26,30